Field Wiring
Block Diagram
Specifications
Modbus Functions and Register List
Calibration
The VP-EC-8AI is an 8 channel analog input module with a Modbus RTU RS485 interface. Each analog input can be jumper configured for:
DIN Rail Enclosures are available in Black, Blue and White
Item | Metric | Value |
---|---|---|
I/O | Part Name : | Channel Analog Input Modbus RTU RS485 Interface |
Part Number : | VPE-5010 | |
Channels : | 8 (Single ended, reference to Common) | |
Input Range (per channel) : | 0 to 20 mA, 0 to 5 VDC, 0 to 10 VDC, Thermistor 10K | |
Over-range limits : | 24 mA, 12 VDC | |
Max. Survivable Input : | 24 mA, 12 VDC | |
Resolution : | 4096 AD Counts (12 bit) | |
Accuracy : | +/- 0.1% mA, +/- 0.1% VDC | |
Input Voltage Drop nominal : | 5 VDC at 20 mA per channel | |
Sample Rate : | 512 ms Default | |
Communication | Protocol : | Modbus RTU RS485 |
Baud Rate | Jumper Selectable 9600,19200 (N81) | |
Modbus ID | 8 Position Dipswitch | |
Termination | Jumper Selectable Enable or Disable 120 Ohm | |
Wiring | 2 sets of terminal blocks (+V, Data A, Data B, Common) | |
Processor | Processor : | STM32 Series |
Field Connections | Terminal Qty : | 33 |
Method : | Screw, Rising Cage Clamp | |
Torque : | 0.753 N-m (4.3 Lb-in) | |
Screw : | M3 | |
Voltage Rating : | 300 VAC | |
Current Rating : | 15 A | |
Withstanding Voltage : | 1.6 KV | |
Cross section solid conductor AWG min : | 28 | |
Cross section solid conductor AWG max : | 12 | |
Cross section stranded conductor AWG min : | 28 | |
Cross section stranded conductor AWG max : | 12 | |
Stripping Length : | 6-7 mm | |
Physical | Length (DIN Enclosure) : | 6.25" |
Width (DIN Enclosure) : | 3.6" | |
Height (DIN Enclosure) : | 2.3" | |
Weight (DIN Enclosure) : | 100 g | |
Weight, Shipping (Qty. 1) : | 200 g | |
Electrical | Power Input Voltage Range (Typical : | 24 VDC |
Power Input (Minimum) : | 9 VDC | |
Power Input (Maximum) : | 28 VDC | |
Current max : | 100 mA (Does Not include Field Transmitters) | |
Current typical : | 75 mA (Does Not include Field Transmitters) | |
Isolation : | None | |
Ambient | Operating Temperature : | -20 to +65 °C |
Storage Temperature : | -40 to +85 °C | |
Operating Relative Humidity (non-condensing) : | 0 to +95 %RH | |
Storage Relative Humidity (non-condensing) : | 0 to +95 %RH | |
Protection : | IP20 | |
Warranty | Limited Liability : | Product Replacement 1 Year |
Download : | Warranty Statement |
Function | Description |
---|---|
Function 03 | Read Holding Registers |
Function 06 | Write Single Holding Register |
Function 16 | Write Multiple Holding Registers |
Address (Dec) | Description |
---|---|
0000 | Input Channel 1 Fault AD Counts |
0001 | Input Channel 2 Fault AD Counts |
0002 | Input Channel 3 Fault AD Counts |
0003 | Input Channel 4 Fault AD Counts |
0004 | Input Channel 5 Fault AD Counts |
0005 | Input Channel 6 Fault AD Counts |
0006 | Input Channel 7 Fault AD Counts |
0007 | Input Channel 8 Fault AD Counts |
0008 | Input Channel 1 Zero (4mA) AD Counts |
0009 | Input Channel 2 Zero (4mA) AD Counts |
0010 | Input Channel 3 Zero (4mA) AD Counts |
0011 | Input Channel 4 Zero (4mA) AD Counts |
0012 | Input Channel 5 Zero (4mA) AD Counts |
0013 | Input Channel 6 Zero (4mA) AD Counts |
0014 | Input Channel 7 Zero (4mA) AD Counts |
0015 | Input Channel 8 Zero (4mA) AD Counts |
0016 | Input Channel 1 Span (20mA) AD Counts |
0017 | Input Channel 2 Span (20mA) AD Counts |
0018 | Input Channel 3 Span (20mA) AD Counts |
0019 | Input Channel 4 Span (20mA) AD Counts |
0020 | Input Channel 5 Span (20mA) AD Counts |
0021 | Input Channel 6 Span (20mA) AD Counts |
0022 | Input Channel 7 Span (20mA) AD Counts |
0023 | Input Channel 8 Span (20mA) AD Counts |
Function | Description |
---|---|
Function 04 | Read Input Registers |
Address (Dec) | Description |
---|---|
0000 | Input Channel 1 AD Counts |
0001 | Input Channel 2 AD Counts |
0002 | Input Channel 3 AD Counts |
0003 | Input Channel 4 AD Counts |
0004 | Input Channel 5 AD Counts |
0005 | Input Channel 6 AD Counts |
0006 | Input Channel 7 AD Counts |
0007 | Input Channel 8 AD Counts |
0008 | Input Channel 1 Percentage 4 to 20 mA as 0 to 100%, Scaled 0 to 1000 |
0009 | Input Channel 2 Percentage 4 to 20 mA as 0 to 100%, Scaled 0 to 1000 |
0010 | Input Channel 3 Percentage 4 to 20 mA as 0 to 100%, Scaled 0 to 1000 |
0011 | Input Channel 4 Percentage 4 to 20 mA as 0 to 100%, Scaled 0 to 1000 |
0012 | Input Channel 5 Percentage 4 to 20 mA as 0 to 100%, Scaled 0 to 1000 |
0013 | Input Channel 6 Percentage 4 to 20 mA as 0 to 100%, Scaled 0 to 1000 |
0014 | Input Channel 7 Percentage 4 to 20 mA as 0 to 100%, Scaled 0 to 1000 |
0015 | Input Channel 8 Percentage 4 to 20 mA as 0 to 100%, Scaled 0 to 1000 |
0016 | Input Channel 1 Reading 4 to 20 mA Scaled 400 to 2000 |
0017 | Input Channel 2 Reading 4 to 20 mA Scaled 400 to 2000 |
0018 | Input Channel 3 Reading 4 to 20 mA Scaled 400 to 2000 |
0019 | Input Channel 4 Reading 4 to 20 mA Scaled 400 to 2000 |
0020 | Input Channel 5 Reading 4 to 20 mA Scaled 400 to 2000 |
0021 | Input Channel 6 Reading 4 to 20 mA Scaled 400 to 2000 |
0022 | Input Channel 7 Reading 4 to 20 mA Scaled 400 to 2000 |
0023 | Input Channel 8 Reading 4 to 20 mA Scaled 400 to 2000 |
The Module comes factory calibrated for 4 – 20 mA Input.
If other input types are used, it is up to the end user to determine their calibration values.